One more thing to watch out for at data centers - fire drills
- Subject: One more thing to watch out for at data centers - fire drills
- From: hcb at netcases.net (hcb at netcases.net)
- Date: Sat, 17 Sep 2016 09:27:26 -0400
On 2016-09-17 08:39, Suresh Ramasubramanian wrote:
> http://motherboard.vice.com/read/a-loud-sound-just-shut-down-a-banks-data-center-for-10-hours?utm_source=bbcfb
>
> Releasing inert gas from fire suppression units that were over
> pressurized resulted in an extremely loud noise ? causing cabinets
> full of hard drives to vibrate ? which got transmitted to the read ?
> write heads of the drives.
>
> Amazing sort of outage + data loss, and this time the physical
> security plant chief gets to write up the RCA.
>
> --srs
Another unexpected result when we had an all-out Halon test: thick fog,
apparently from cold gas and somewhat humid air. I'm glad to have been
watching through windows. Visibility in the room dropped to zero.